Identifying Motors
Identifying Motors
Electric motors with no
identification (no nameplate or lead tags) must often be maintained and
repaired. Follow these steps to determine an unknown motor’s characteristics,
based on the NEMA Standard method of motor identification. First, sketch the
coils to form a wye. Identify one outside coil end with the number one (1), and
then draw a decreasing spiral and number each coil end in sequence as shown in
Figure 6-3.
Using a DMM, ohmmeter, or continuity
tester, the individual circuits can then be identified as follows:
Step 1. Connect one probe of the tester to
any lead, and check for continuity to each of the other eight leads. A reading
from only one other lead indicates one of the two-wire circuits. A reading to
two other leads indicates the three-wire circuit that makes up the internal wye
connection.
Step 2. Continue checking and isolating
leads until all four circuits have been located Tag the wires of the three lead
circuits T-7, T-8, and T-9 in any order. The other leads should be temporarily
marked T-1 and T-4 for one circuit, T-2 and T-5 for the second circuit, and T-3
and T-6 for the third and final circuit.
The following test voltages are for the most common
dual-voltage range of 230/460 V. For other motor ranges, the voltages listed
should be changed in proportion to the motor rating.

6-3 Identify one
outside coil and then draw a decreasing spiral and number each coil.
As all the coils are physically
mounted in slots on the same motor frame, the coils will act almost like the primary
and secondary coils of a transformer. Figure 6-4 shows a simplified electrical
arrangement of the coils. Depending on which coil group power is applied to,
the resulting voltage readings will be additive, subtractive, balanced, or unbalanced
depending on physical location with regard to the coils themselves.

6-4 Simplified
electrical arrangement of wye-wound motor coils.
Step 3. The motor may be started on 230 V by
connecting leads T-7, T-8, and T-9 to the three-phase source. If the motor is
too large to be connected directly to the line, the voltage should be reduced
by using a reduced voltage starter or other suitable means.
Step 4. Start the motor with no load
connected and bring up to normal speed.
Step 5. With the motor running, a voltage
will be induced in each of the open two-wire circuits that were tagged T-1 and
T-4, T- 2 and T-5, and T-3 and T-6. With a voltmeter, check the voltage reading
of each circuit. The voltage should be approximately 125 to 130 V and should be
the same on each circuit.
Step 6. With the motor still running,
carefully connect the lead that was temporarily marked T-4 with the T-7 and
line lead.
Read the voltage between T-1 and T-8 and also between T-1 and
T-9. If both readings are of the same value and are approximately 330 to 340 V,
leads T-1 and T-4 may be disconnected and permanently marked T-1 and T-4.
Step 7. If the two voltage readings are of
the same value and are approximately 125 to 130 V, disconnect and interchange leads.
If the test calls for equal voltages of 125 to130 V and the reading is only 80
to 90 V, this is acceptable as long as the voltage readings are nearly equal.
T- 1 and T-4 and mark permanently (original T-1 changed to T-4 and original T-4
changed to T-1).
Step 8. If readings between T-1 and T-8 and between
T-1 and T-9 are of unequal values, disconnect T-4 from T-7 and reconnect T-4 to
the junction of T-8 and line.
Step 9. Measure the voltage now between T-1 and
T-7 and also between T-1 and T-9. If the voltages are equal and approximately 330
to 340 V, tag T-1 is permanently marked T-2 and T-4 is marked T-5 and
disconnected. If the readings taken are equal but are approximately 125 to 130
V, leads T-1 and T-4 are disconnected, interchanged, and marked T-2 and T-5
(T-1 changed to T-5, and T- 4 changed to T-2). If both voltage readings are
different, T-4 lead is disconnected from T-8 and moved to T- 9. Voltage
readings are taken again (between T-1 and T-7 and T-1 and T-8) and the leads
permanently marked T-3 and T-6 when equal readings of approximately 330 to 340
V are obtained.
Step 10. Follow the same procedure for the other
two circuits that were temporarily marked T-2 and T-5 and T-3 and T-6, until a
position is found where both voltage readings are equal and approximately 330
to 340 V and the tags change to correspond to the standard lead markings as
shown in Figure 6-5.

6-5 NEMA Standard lead
markings for dual-voltage, wye-wound motors.
Step 11. Once all leads have been properly
and permanently tagged, leads T-4, T-5, and T-6 are connected together and
voltage readings are taken between T-1, T-2, and T-3. The voltages should be
equal and approximately 230 V.
Step 12. As an additional check, the motor is
shut down and leads T-7, T-8, and T-9 are disconnected, and leads T-1, and T-3
are connected to the line.
Connect T-1 to the line lead T-7 was connected to, T-2 to the
same line as T-8 was previously connected to, and T-3 to the same lead that T-9
was connected to. With T-4, T-5, and T-6 still connected together to form a wye
connection, the motor can again be started without a load. If all lead markings
are correct, the motor rotation with leads T-1, T-2, and T-3 connected will be
the same as when T-7, T-8, and T-9 were connected.
The motor is
now ready for service and is connected in series for high voltage or parallel
for low as indicated by the NEMA Standard connections shown in Figure 6-6.
Three-Phase Delta-Wound Motors
Most dual-voltage, delta-wound motors
also have nine leads, as indicated in Figure 6-6, but there are only three
circuits of three leads each. Use continuity tests to find the three coil
groups, as was done for the wye-wound motor. Once the coil groups are located and
isolated, make further resistance checks to locate the common wire in each coil
group. A DMM, Wheatstone bridge, or other sensitive device may be needed, since
the resistance of some delta-wound motors is very low.

6-6 NEMA Standard lead
markings for dual-voltage, delta-wound motors.
Each coil group consists of two coils
tied together with three leads brought out to the motor junction or terminal
box. Reading the resistance carefully between each of the three leads shows
that the readings from one of the leads to each of the other two leads will be
the same (equal), but the resistance reading between those two leads will be
double the previous readings; Figure 6-7 illustrates the technique:
Step 1. The common lead found in the first
coil group is permanently marked T-1, and the other two leads temporarily
marked T-4 and T-9. The common lead of the next coil group is found and
permanently marked T-2 and the other leads temporarily marked T-5 and T-7. The common
lead of the last coil group is located and marked T-3 with the other leads being
temporarily marked T-6 and T-8.
Step 2. After the leads have been marked,
connect the motor to a 230-V three-phase line using leads T-1, T-4, and T-9.
Lead T-7 is connected to line and T-4, and the motor is started with no load
connected. Voltage readings are taken between T-1 and T-2. If the voltage is
approximately 460 V, the markings are correct and may be permanently marked.
Step 3. If the voltage reading is 400 V or
less, interchange T-5 and T-7 or T-4 and T-9 and read the voltage again. If the
voltage is approximately 230 V, interchange both T-5 with T-7 and T-4 with T-9.
The readings should now be approximately 460 V between leads T-1 and T-2. The
leads connected together now are actually T-4 and T-7 and are marked
permanently. The remaining lead in each group can now be marked T-9 and T-5, as
indicated by Figure 6-7.
Step 4. Connect one of the leads of the last
coil group (not T-3) to T-9. If the reading is approximately 460 V between T-1
and T-3, permanently mark this lead T-6. If the reading is 400 V or less,
interchange T-6 and T-8. A reading now of 460 V should exist between T-1 and
T-3. T-6 is changed to T-8 and marked permanently and temporary T-8 is changed
to T-6.

6-7 Using DMM to test
motor leads.
If all leads are now correctly marked, equal readings of approximately
460 V can be obtained between leads T-1, T-2, and T-3.
Step 5. To double-check these markings,
shut off the motor and reconnect it using T-2, T-5, and T-7. Connect T-2 to the
same line lead as T-1, connect T-5 where T-4 was, and connect T-7 where T-9 was
previously connected. When started, the motor should rotate the same direction
as before.
Step 6. Stop the motor and connect leads
T-3, T-6, and T-8 to the line leads previously connected to T-2, T-5, and T-7,
respectively, and when the motor is started it should still rotate in the same
direction. The motor is now ready for service and is connected in series for
high or parallel for low voltage as indicated by the NEMA Standard connections
shown in Figure 6-6.
Komentar
Posting Komentar