Identifying Motors

 

Identifying Motors

 

Electric motors with no identification (no nameplate or lead tags) must often be maintained and repaired. Follow these steps to determine an unknown motor’s characteristics, based on the NEMA Standard method of motor identification. First, sketch the coils to form a wye. Identify one outside coil end with the number one (1), and then draw a decreasing spiral and number each coil end in sequence as shown in Figure 6-3.

Using a DMM, ohmmeter, or continuity tester, the individual circuits can then be identified as follows:

Step 1. Connect one probe of the tester to any lead, and check for continuity to each of the other eight leads. A reading from only one other lead indicates one of the two-wire circuits. A reading to two other leads indicates the three-wire circuit that makes up the internal wye connection.

Step 2. Continue checking and isolating leads until all four circuits have been located Tag the wires of the three lead circuits T-7, T-8, and T-9 in any order. The other leads should be temporarily marked T-1 and T-4 for one circuit, T-2 and T-5 for the second circuit, and T-3 and T-6 for the third and final circuit.

The following test voltages are for the most common dual-voltage range of 230/460 V. For other motor ranges, the voltages listed should be changed in proportion to the motor rating.

6-3 Identify one outside coil and then draw a decreasing spiral and number each coil.

 

As all the coils are physically mounted in slots on the same motor frame, the coils will act almost like the primary and secondary coils of a transformer. Figure 6-4 shows a simplified electrical arrangement of the coils. Depending on which coil group power is applied to, the resulting voltage readings will be additive, subtractive, balanced, or unbalanced depending on physical location with regard to the coils themselves.

6-4 Simplified electrical arrangement of wye-wound motor coils.

Step 3. The motor may be started on 230 V by connecting leads T-7, T-8, and T-9 to the three-phase source. If the motor is too large to be connected directly to the line, the voltage should be reduced by using a reduced voltage starter or other suitable means.

Step 4. Start the motor with no load connected and bring up to normal speed.

Step 5. With the motor running, a voltage will be induced in each of the open two-wire circuits that were tagged T-1 and T-4, T- 2 and T-5, and T-3 and T-6. With a voltmeter, check the voltage reading of each circuit. The voltage should be approximately 125 to 130 V and should be the same on each circuit.

Step 6. With the motor still running, carefully connect the lead that was temporarily marked T-4 with the T-7 and line lead.

Read the voltage between T-1 and T-8 and also between T-1 and T-9. If both readings are of the same value and are approximately 330 to 340 V, leads T-1 and T-4 may be disconnected and permanently marked T-1 and T-4.

Step 7. If the two voltage readings are of the same value and are approximately 125 to 130 V, disconnect and interchange leads. If the test calls for equal voltages of 125 to130 V and the reading is only 80 to 90 V, this is acceptable as long as the voltage readings are nearly equal. T- 1 and T-4 and mark permanently (original T-1 changed to T-4 and original T-4 changed to T-1).

Step 8. If readings between T-1 and T-8 and between T-1 and T-9 are of unequal values, disconnect T-4 from T-7 and reconnect T-4 to the junction of T-8 and line.

Step 9. Measure the voltage now between T-1 and T-7 and also between T-1 and T-9. If the voltages are equal and approximately 330 to 340 V, tag T-1 is permanently marked T-2 and T-4 is marked T-5 and disconnected. If the readings taken are equal but are approximately 125 to 130 V, leads T-1 and T-4 are disconnected, interchanged, and marked T-2 and T-5 (T-1 changed to T-5, and T- 4 changed to T-2). If both voltage readings are different, T-4 lead is disconnected from T-8 and moved to T- 9. Voltage readings are taken again (between T-1 and T-7 and T-1 and T-8) and the leads permanently marked T-3 and T-6 when equal readings of approximately 330 to 340 V are obtained.

Step 10. Follow the same procedure for the other two circuits that were temporarily marked T-2 and T-5 and T-3 and T-6, until a position is found where both voltage readings are equal and approximately 330 to 340 V and the tags change to correspond to the standard lead markings as shown in Figure 6-5.

6-5 NEMA Standard lead markings for dual-voltage, wye-wound motors.

Step 11. Once all leads have been properly and permanently tagged, leads T-4, T-5, and T-6 are connected together and voltage readings are taken between T-1, T-2, and T-3. The voltages should be equal and approximately 230 V.

 

 

 

Step 12. As an additional check, the motor is shut down and leads T-7, T-8, and T-9 are disconnected, and leads T-1, and T-3 are connected to the line.

Connect T-1 to the line lead T-7 was connected to, T-2 to the same line as T-8 was previously connected to, and T-3 to the same lead that T-9 was connected to. With T-4, T-5, and T-6 still connected together to form a wye connection, the motor can again be started without a load. If all lead markings are correct, the motor rotation with leads T-1, T-2, and T-3 connected will be the same as when T-7, T-8, and T-9 were connected.

The motor is now ready for service and is connected in series for high voltage or parallel for low as indicated by the NEMA Standard connections shown in Figure 6-6.

Three-Phase Delta-Wound Motors

Most dual-voltage, delta-wound motors also have nine leads, as indicated in Figure 6-6, but there are only three circuits of three leads each. Use continuity tests to find the three coil groups, as was done for the wye-wound motor. Once the coil groups are located and isolated, make further resistance checks to locate the common wire in each coil group. A DMM, Wheatstone bridge, or other sensitive device may be needed, since the resistance of some delta-wound motors is very low.

6-6 NEMA Standard lead markings for dual-voltage, delta-wound motors.

 

 

 

 

 

Each coil group consists of two coils tied together with three leads brought out to the motor junction or terminal box. Reading the resistance carefully between each of the three leads shows that the readings from one of the leads to each of the other two leads will be the same (equal), but the resistance reading between those two leads will be double the previous readings; Figure 6-7 illustrates the technique:

Step 1. The common lead found in the first coil group is permanently marked T-1, and the other two leads temporarily marked T-4 and T-9. The common lead of the next coil group is found and permanently marked T-2 and the other leads temporarily marked T-5 and T-7. The common lead of the last coil group is located and marked T-3 with the other leads being temporarily marked T-6 and T-8.

Step 2. After the leads have been marked, connect the motor to a 230-V three-phase line using leads T-1, T-4, and T-9. Lead T-7 is connected to line and T-4, and the motor is started with no load connected. Voltage readings are taken between T-1 and T-2. If the voltage is approximately 460 V, the markings are correct and may be permanently marked.

Step 3. If the voltage reading is 400 V or less, interchange T-5 and T-7 or T-4 and T-9 and read the voltage again. If the voltage is approximately 230 V, interchange both T-5 with T-7 and T-4 with T-9. The readings should now be approximately 460 V between leads T-1 and T-2. The leads connected together now are actually T-4 and T-7 and are marked permanently. The remaining lead in each group can now be marked T-9 and T-5, as indicated by Figure 6-7.

Step 4. Connect one of the leads of the last coil group (not T-3) to T-9. If the reading is approximately 460 V between T-1 and T-3, permanently mark this lead T-6. If the reading is 400 V or less, interchange T-6 and T-8. A reading now of 460 V should exist between T-1 and T-3. T-6 is changed to T-8 and marked permanently and temporary T-8 is changed to T-6.

6-7 Using DMM to test motor leads.

 

If all leads are now correctly marked, equal readings of approximately 460 V can be obtained between leads T-1, T-2, and T-3.

Step 5. To double-check these markings, shut off the motor and reconnect it using T-2, T-5, and T-7. Connect T-2 to the same line lead as T-1, connect T-5 where T-4 was, and connect T-7 where T-9 was previously connected. When started, the motor should rotate the same direction as before.

Step 6. Stop the motor and connect leads T-3, T-6, and T-8 to the line leads previously connected to T-2, T-5, and T-7, respectively, and when the motor is started it should still rotate in the same direction. The motor is now ready for service and is connected in series for high or parallel for low voltage as indicated by the NEMA Standard connections shown in Figure 6-6.

 

 

 

 

Komentar

Postingan populer dari blog ini

Troubleshooting Relays and Contactors