Identifying Motors

Gambar
  Identifying Motors   Electric motors with no identification (no nameplate or lead tags) must often be maintained and repaired. Follow these steps to determine an unknown motor’s characteristics, based on the NEMA Standard method of motor identification. First, sketch the coils to form a wye. Identify one outside coil end with the number one (1), and then draw a decreasing spiral and number each coil end in sequence as shown in Figure 6-3. Using a DMM, ohmmeter, or continuity tester, the individual circuits can then be identified as follows: Step 1. Connect one probe of the tester to any lead, and check for continuity to each of the other eight leads. A reading from only one other lead indicates one of the two-wire circuits. A reading to two other leads indicates the three-wire circuit that makes up the internal wye connection. Step 2. Continue checking and isolating leads until all four circuits have been located Tag the wires of the three lead circuits T-7, T-8,...

Maintenance philosophies batteries.

 

Maintenance philosophies batteries.  

 

There are different philosophies and ambition levels for maintaining and testing batteries. Some examples:

1.      Just replace batteries when they fail or die. Minimum or no maintenance and testing. Obviously, not testing batteries at all is the least costly with considering only maintenance costs but the risks are great. The consequences must be considered when evaluating the cost-risk analysis since the risks are associated with the equipment being supported. Batteries have a limited lifetime and they can fail earlier than expected. Time between outages is usually long and if outages are the only occasions the battery shows its capability risk is high that reduced or no back-up is available when needed. Having batteries as back-up of important installations without any idea of their current health spoils the whole idea of a reliable system.

2.      Replace after a certain time. Minimum or no maintenance and testing. This might also be a risky approach. Batteries can fail earlier than expected. Also it is waste of capital if the batteries are replaced earlier than needed. Properly maintained batteries can live longer than the predetermined replacement time.

3.      A serious maintenance and testing program in order to ensure the batteries are in good condition, prolong their life and to find the optimal time for replacement . A maintenance program including inspection, impedance and capacity testing is the way to track the battery’s state of health. Degradation and faults will be found before they become serious and surprises can be avoided. Maintenance costs are higher but this is what you have to pay for to get the reliability you want for your back-up system.

The best testing scheme is the balance between maintenance costs and risks of losing the battery and the supported equipment. For example, in some transmission substations, there is upwards of $10 million per hour flowing through them. What is the cost of not maintaining battery systems in those substations? A $3000 battery is fairly insignificant compared to the millions of dollars in lost revenues. Each company is different and must individually weigh the cost risk of battery maintenance.


How to maintain the battery

 

Standards and common practices

There are a number of standards and company practices for battery testing. Usually they comprise inspections (observations, actions and measurements done under normal float condition) and capacity tests. Most well-known are the

IEEE standards:

Ø  IEEE 450 for flooded lead-acid

Ø  IEEE 1188 for sealed lead-acid

Ø  IEEE 1106 for nickel-cadmium

 

IEEE 450

IEEE 450, “IEEE Recommended Practice for Maintenance,

Testing and Replacement of Vented Lead-acid Batteries for Stationary Applications” describes the frequency and type of measurements that need to be taken to validate the condition of the battery. The standard covers Inspections, Capacity test, Corrective actions, Battery replacement criteria etc.

Inspections

Ø  Monthly inspection include appearance and measurements of string voltage, ripple voltage, ripple current, charger output current and voltage, ambient temperature, voltage and electrolyte temperature at pilot cells, battery float charging current or specific gravity at pilot cells, unintentional battery grounds etc.

Ø  Quarterly inspections include same measurements as monthly inspection and in addition voltage of each cell, battery float charging current or specific gravity of 10% of the cells or float current, and electrolyte temperature (≥10% of cells).

Ø  Once a year a quarterly inspection should be extended with measurement of float charging current or specific gravity of all cells, temperature of each cell, cell-to-cell and terminal connection resistance are performed on the entire string.

 

Capacity test (discharge test) should be done

Ø  At the installation (acceptance test)

Ø  Within the first two years of service

Ø  Periodically. Intervals should not be greater than 25% of the expected service life.

Ø  Annually when the battery shows signs of degradation or has reached 85% of the expected service life. Degradation is indicated when the battery capacity drops more than 10% from its capacity on the previous capacity test or is below 90% of manufacturers rating. If the battery has reached 85% of service life, delivers 100% or greater of the manufacturer's rated capacity and has no signs of degradation it can be tested at two-year Intervals until it shows signs of degradations.


IEEE 1188

IEEE 1188, “IEEE Recommended Practice for Maintenance, Testing and Replacement of Valve-Regulated Lead-Acid Batteries for Stationary Applications” defines the recommended tests and frequency.

 

Inspections

Ø  Monthly inspection include battery terminal float voltage, charger output current and voltage, ambient temperature, visual inspection and DC float current per string.

Ø  Quarterly same measurements as for monthly inspection shall be done and additionally cell/unit impedance value, temperature of negative terminal of each cell and voltage of each cell. For applications with a discharge rate of one hour or less, resistance of 10% of the intercell connections shall be measured.

Ø  Annually above measurements should be taken and in addition Cell-to-cell and terminal connection resistance of entire battery and AC ripple current and/or voltage imposed on the battery.

Capacity test (capacity test) should be done

Ø  At the installation (acceptance test)

Ø  Periodically. Intervals should not be greater than 25% of the expected service life or two years, whichever is less.

Ø  Where impedance values has changed significantly between readings or physically changes has occurred

Ø  Annually when the battery shows signs of degradation or has reached 85% of the expected service life. Degradation is indicated when the battery capacity drops more than 10% from its capacity on the previous capacity test or is below 90% of manufacturers rating.

 

Battery replacement criteria

Both IEEE 450 and IEEE 1188 recommend replacing the battery if its capacity is below 80% of manufacturer’s rating. Maximum time for replacement is one year. Physical characteristics such as plate condition or abnormally high cell temperatures are often determinants for complete b

 

IEEE 1106

IEEE 1106, “IEEE Recommended Practice for Installation, Maintenance, Testing and Replacement of Vented Nickel-Cadmium Batteries for Stationary Applications”.

 

Inspections

Ø  Inspection at least once per quarter include battery terminal float voltage, appearance, charger output current and voltage, pilot-cell electrolyte temperature.

Ø  Semi-annually general inspection and measurement of voltage of each cell shall be done.

Capacity test (discharge test) should be done

Ø  Within the first two years of service

Ø  At 5-year intervals until the battery shows signs of excessive capacity loss.

Ø  Annually at excessive capacity loss

 

 

Summary best way to test and evaluate your battery

 

Test intervals

1.      Make a capacity test when the battery is new as part of the acceptance test.

2.      Make an impedance test at the same time to establish baseline values for the battery.

3.      Repeat the above within 2 years for warranty purpose.

4.      Make an impedance test every year on flooded cells and quarterly on VRLA cells.

5.      Make capacity tests at least for every 25% of expected service life.

6.      Make capacity test annually when the battery has reached 85% of expected service life or if the capacity has dropped more than 10% since the previous test or is below 90% of the manufacturers rating.

7.      Make a capacity test if the Impedance value has changed significantly.

8.      Follow a given practice (preferably from the IEEE standard) for all temperature, voltage, gravity measurements etc. and fill in a report. This will be a great help for trending and for fault tracing.

 

Evaluation

1.      Replace cell if the impedance is more than 50% above baseline. Make a capacity test if 20-50% of baseline.

2.      Replace battery if capacity test shows less than 80% of rated capacity.

 

 

Komentar

Postingan populer dari blog ini

Troubleshooting Relays and Contactors