Identifying Motors
Troubleshooting
Dry-Type Transformers
Dry-type transformers are a part of
most electrical installations. They range in size from small doorbell transformers
to three-phase 25-kVA units installed in electrical closets (Figure 4-1) to
large, free-standing units rated at several hundred kVA (Figure 4-2).
Electricians must know how to test for and diagnose problems that develop in
transformers—especially in the smaller, dry type power-supply or control
transformers.
Open Circuit
If one of the windings in a
transformer develops a break or “open” condition, no current can flow and therefore,
the transformer will not deliver any output. The symptom of an open-circuited
transformer is that the circuits, which derive power from the transformer, are
de-energized or “dead.” Use an AC voltmeter or DMM to check across the
transformer output terminals, as shown in Figure 4-3. A reading of 0 V
indicates an open circuit.
Then take a voltage reading across
the input terminals. If voltage is present, this indicates that one of the
transformer windings is open. However, if there is no voltage reading on the
input terminals either, then the open must be somewhere else on the line side
of the circuit; possibly a disconnect switch is open.

4-1 Dry-type
transformer (25-kVA, three-phase).

4-2 Dry-type
transformer (300-kVA, three-phase)
Note:
Make absolutely certain
that your testing instruments are designed for the job and are calibrated for
the correct voltage. Never test the primary side of any transformer over 600 V
unless you are qualified, have the correct high-voltage testing instruments,
and the test is made under the proper supervision.

4-3. checking for an
open circuit in a transformer.
However, if voltage is present on the
line or primary side and no voltage is on the secondary or load side, open the
switch to de-energize the circuit, and place a warning tag (tag-out and lock)
on this switch so that it is not inadvertently closed again while someone is
working on the circuit. Disconnect all of the transformer primary and secondary
leads and check each winding in the transformer for continuity (a continuous
circuit), as indicated by a resistance reading taken with an ohmmeter.
Continuity is indicated by a
relatively low resistance reading on control transformers, while an open
winding will be indicated by an infinite resistance reading (OL or 1). In most
cases, such small transformers will have to be replaced, unless of course the
break is accessible and can be repaired.
Ground Fault
Sometimes a few turns in the
secondary winding of a transformer experience a partial short, which in turn causes
a voltage drop across the secondary. The usual symptom of this condition is
transformer overheating caused by large circulating currents flowing in the shorted
windings.
The easiest way to check this
condition is with a voltmeter. Take a reading on the line or primary side of the
transformer first to make certain normal voltage is present. Then take a reading
on the secondary side. If the transformer has a partial short or ground fault,
the secondary voltage reading will be lower than normal.
Replace the faulty transformer with a
new one and again take a reading on the secondary. If the voltage reading is
now normal and the circuit operates satisfactorily, leave the replacement
transformer in the circuit, and either discard or repair the original
transformer.
Complete Short
Occasionally a transformer winding
becomes completely shorted. In most cases, this activates the overcurrent-protective
device (circuit breaker or fuse) and de-energizes the circuit. But in some
cases, the transformer may continue trying to operate with excessive
overheating—due to the very large circulating current. This heat will often melt
the insulation inside the transformer, which is easily detected by the odor.
Also, there will be no voltage output across the shorted winding and the
secondary circuit supplied by that winding will be dead.
The short may be in the external
secondary circuit or it may be in the transformer’s winding. To determine its location,
disconnect the secondary circuit from the winding and take a reading with a
voltmeter. If the voltage is normal with the external circuit disconnected, then
the problem is in the external circuit. However, if the voltage reading is still
zero across the secondary leads, the transformer is shorted and must be
replaced.
Grounded Windings
Insulation breakdown is quite common
in older transformers—especially those that have been overloaded. At some
point, insulation breaks or deteriorates and bare conductors become exposed.
The exposed wire often comes into contact with the transformer housing and
grounds the winding.
If a winding develops a ground, and a
point in the external circuit connected to this winding is also grounded, part
of the winding will be shorted out. The symptoms are overheating, usually
detected by feel or smell, and a low voltage reading as indicated on a
voltmeter scale. In most cases, transformers with this condition must be
replaced.
A mega ohmmeter is used to test for
this condition. Disconnect the leads from both the primary and secondary windings.
Tests can then be performed on either winding by connecting the megger negative
test lead to an associated ground and the positive test lead to the winding to
be measured.
Insulation resistance should then be
measured between the windings themselves, by connecting one test lead to the
primary and the second test lead to the secondary.
The troubleshooting chart in Figure 4-4 covers the most
common dry-type transformer problems.


4-4 troubleshooting
chart for dry-type transformers.
Komentar
Posting Komentar