Identifying Motors
Troubleshooting
Electric Motors
Electric motors operate on the
principle of electromagnetic induction. An electric motor has a stationary magnet,
or stator, with windings connected to the supply conductors, and a rotating
magnet. There is no electrical connection between the stator and rotor. The
magnetic field produced in the stator windings induces a voltage in the rotor.
When an electric motor malfunctions,
the stator (stationary) windings are often defective, and must be repaired or
replaced. Stator problems are usually caused by one or more of the following:
Ø Worn bearings
Ø Moisture
Ø Overloading
Ø Poor insulation
Ø Single-phase operation of a
three-phase motor
Troubleshooting Motors
To detect defects in electric motors,
the windings are normally tested for ground faults, opens, shorts, and reverses.
The exact method of performing these tests depends on the type of motor being
serviced. However, regardless of the motor type, a knowledge of some important
terms is necessary to properly troubleshoot motors:
Ground :
A winding becomes grounded when it makes an electrical contact with the iron
frame of the motor. The usual causes of grounds include bolts securing the end
plates coming into contact with the winding; wires press against laminations at
the corners of the slots; or the centrifugal switch becoming grounded to the
end plate.
Open circuits :
Loose or dirty connections, as well as a broken wire, can cause an open circuit
in an electric motor.
Shorts :
If two or more turns of a winding contact each other, the result is an
electrical short circuit. This condition may develop in a new winding if the
winding is tight and pounding is necessary to place the wires in position. In
other cases, excessive heat caused by overloads degrades the insulation and
causes a short. A short circuit is often detected by observing smoke from the
windings as the motor operates, or if the motor draws excessive current at no
load.
The chart in Figure 6-1 lists tools
and equipment used in maintenance and troubleshooting of electric motors. The
following sections describe common causes of motor malfunctions.



6-1 Tools for electric
motor maintenance.
Grounded Coils
A grounded coil in a motor winding typically causes repeated
tripping of the circuit breaker. Follow these steps to test for a grounded coil
using a continuity tester:
1.
Open
and lock out the disconnecting means, to insure the motor is de-energized.
2.
Place
one test lead on the frame of the motor and the other in turn on each of the
ungrounded (power) conductor supplying the motor. If there is a grounded coil
at any point in the winding, the lamp of the continuity tester will light, or
the meter display will indicate infinity.
3.
For
a three-phase motor, test each phase separately, after disconnecting the star
or delta connection.
4.
Sometimes
moisture on old insulation around the coils causes a high-resistance ground
that is difficult to detect with a test lamp. A megger can be used to detect
such faults.
5.
Test
the armature windings and commutator for grounds in a similar manner.
6.
On
some motors, the brush holders are grounded to the end plate. Before the
armature is tested for grounds, lift the brushes away from the commutator.
Shorted Coils
Shorted turns within coils are
usually the result of failure of the insulation on the wires, caused by oil,
moisture, and the like. One inexpensive way of locating a shorted coil is by
the use of a growler and a thin piece of steel, as shown in Figure 6-2.
6-2 Growler used to test a stator of an AC motor.
1.
Place
the growler in the core as shown, with the thin piece of steel at the distance
of one coil span from the center of the growler.
2.
Test
the coils by moving the growler around the bore of the stator and always
keeping the steel strip the same distance away from it.
3.
If
any coil has one or more shorted turns, the piece of steel will vibrate very
rapidly and cause a loud humming noise. By locating the two slots over which
the steel vibrates, both sides of the shorted coil can be found.
4.
Sometimes
one coil or a complete coil group becomes short-circuited at the end
connections. The test for this fault is the same as that for a shorted coil.
Open Circuit
1.
When
one or more coils become open-circuited by a break in the turns or a poor
connection at the end, they can be tested with a continuity tester as
previously explained. If this test is made at the ends of each winding, an open
can be detected by the lamp failing to light. Remove the insulation from the
pole-group connections, and test each group separately.
2.
An
open circuit in the starting winding may be difficult to locate, since the
problem may be in the centrifugal switch instead of the winding itself. In
fact, the centrifugal switch is more likely to cause trouble than the winding
since parts become worn, defective, and more likely, dirty. Insufficient
pressure of the rotating part of centrifugal switches against the stationary
part will prevent the contacts from closing and thereby produce an open
circuit.
Reversed Coil Connections
Reversed connections cause current to
flow through coils in the wrong direction. This causes disturbance of the
magnetic circuit, which results in excessive noise and vibration.
The fault can be located by the use
of a magnetic compass and a direct current power source, as follows:
1.
Adjust
to send about one-fourth to one-sixth of the full-load current through the
winding, with the DC
leads placed on the start and finish of one phase.
2.
If
the winding is a three-phase, star-connected, winding this is at the start of
one phase and the star point. If the winding is delta-connected, disconnect the
delta point and test each phase separately.
3.
Place
a compass on the inside of the stator and test each coil group in that phase.
If the phase is connected correctly, the needle of the compass will reverse
definitely as it is moved from one coil group to another. However, if any one
of the coils is reversed, the reversed coil will build up a field in the
direction opposite to the others, thus causing a neutralizing effect that is
indicated by the compass needle refusing to point definitely to that group. If
there are only two coils per group, there will be no indication if one of them
is reversed, as that group will be completely neutralized.
4.
When
an entire coil group is reversed, current flows in the wrong direction in that
whole group. The test for this fault is the same as that for reversed coils.
Magnetize the winding with DC, and when the compass needle is passed around the
coil group, it should alternately indicate North-South, North-South, and so on.
Reversed Phase
Sometimes in a three-phase winding a
complete phase is reversed by either having taken the starts from the wrong
coils or connecting one of the windings in the wrong relation to the others
when making the star or delta connections.
Delta connection: In a delta-connected winding, disconnect
any one of the points where the phases are connected together and pass current
through the three windings in series. Place a compass on the inside of the
stator and test each coil group by slowly moving the compass one complete
revolution around the stator. The reversals of the needle in moving the compass
one revolution around the stator should be three times the number of poles in
the winding.
Wye connection: In a star- or wye-connected winding,
connect the three starts together and place them on one DC lead. Then connect
the other DC lead and star point, thus passing the current through all three
windings in parallel. Test with a compass in the same way as the delta winding.
The result should then be the same, or the reversals of the needle in making
one revolution around the stator should again be three times the number of
poles in the winding.
These tests for reversed phases apply
to full-pitch windings only. If the winding is fractional-pitch, a careful
visual check should be made to determine whether there is a reversed phase or
mistake in connecting the star or delta connections.
Komentar
Posting Komentar