Identifying Motors
Troubleshooting
Split-Phase Motors
If a split-phase motor fails to start, the trouble may be due
to one or more of the following faults:
o
Tight
or “frozen” bearings
o
Worn
bearings, allowing the rotor to drag on the stator
o
Bent
rotor shaft
o
One
or both bearings out of alignment
o
Open
circuit in either starting or running windings
o
Defective
centrifugal switch
o
Improper
connections in either winding
o
Grounds
in either winding or both
o
Shorts
between the two windings
Tight or worn bearings
Tight or worn bearings may be due to
the lubricating system failing, or when new bearings are installed, they may
run hot if the shaft is not kept well oiled. If the bearings are worn to such
an extent that they allow the rotor to drag on the stator, this will usually
prevent the rotor from starting. The inside of the stator laminations will be
worn bright where they are rubbed by the rotor. When this condition exists, it
can generally be easily detected by close observation of the stator field and
rotor surface when the rotor is removed.
Bent shaft and bearings
out of alignment
A bent rotor shaft will usually cause
the rotor to bind in a certain position but then run freely until it comes back
to the same position again. Test for a bent shaft by placing the rotor between
centers on a lathe and turning the rotor slowly while a tool or marker is held in the tool post close
to the surface of the rotor. If the rotor wobbles, it is an indication of a
bent shaft. Bearings out of alignment are usually caused by uneven tightening
of the end-shield plates. When placing end shields or brackets on a motor,
tighten the bolts alternately, first drawing up two bolts, which are
diametrically opposite.
Open circuits and defective
centrifugal switches
Open circuits in either the starting
or running winding will prevent the motor from starting. This fault can be detected
by testing in series with the start and finish of each winding with a test lamp
or ohmmeter.
A defective centrifugal switch is
generally caused by dirt, grit, or some other foreign matter getting into the
switch. The switch should be thoroughly cleaned with a degreasing solution and
then inspected for weak or broken springs. If the winding is on the rotor, the
brushes sometimes stick in the holders and fail to make good contact with the
slip rings. This causes sparking at the brushes. There will probably also be a
certain place where the rotor will not start until it is moved far enough for
the brush to make contact on the ring. The brush holders should be cleaned and
the brushes carefully fitted so they move more freely with a minimum of
friction between the brush and the holders.
Reversed connections and grounds
Reversed connections are caused by improperly
connecting a coil or group of coils. The wrong connections can be found and
corrected by making a careful check on the connections and reconnecting those
that are found at fault. The compass test with a DC power source can also be
used for locating reversed coils. Test the starting and running windings
separately, exciting only one winding at a time, with direct current. The
compass should show alternate poles around the winding.
The operation of a motor that has a
ground in the winding will depend on where the ground is and whether or not the
frame is grounded. If the frame is grounded, then when the ground occurs in the
winding, it will usually blow a fuse or trip the overcurrent protective device.
A test for grounds can be made with a
test lamp or continuity tester. One test lead should be placed on the frame and
the other on a lead to the winding. If there is no ground, the lamp will not
light, nor will any deflection be present when a meter is used. If the lamp
does light or the meter shows continuity, it indicates a ground is present—due
to a defect somewhere in the motor’s insulation.
Short circuits
Short circuits between any two
windings can be detected by the use of a test lamp or continuity tester. Place
one of the test leads on one wire of the starting winding and the other test
lead on the wire of the running winding. If these windings are properly
insulated from each other, the lamp should not light. If it does, it is a certain
indication that a short or ground fault exists between the windings. Such a
condition will usually cause part of the starting winding to burn out. The starting
winding is always wound on top of the running winding, so a defective starting winding
can be conveniently removed and replaced without disturbing the running
winding.
Komentar
Posting Komentar